Full system cleaning and a UV light with carbon filter
A maintenance plan visit on a gas furnace with central AC. The duct plenum was coated in dust, so we vacuumed it out, cleaned the burners, blower wheel and evaporator coil, replaced a weak capacitor and installed a UV light with a carbon filter.
Findings and readings
- A heavy layer of dust across the floor of the duct plenum.
- Dust and debris on the blower wheel and in the burner compartment.
- The evaporator coil was due for a flush.
- A weak 5 µF capacitor.
| Check | Reading | Result |
|---|---|---|
| Duct plenum | Heavy dust | Vacuumed |
| Blower wheel | Dirty | Cleaned |
| Capacitor (5 µF) | Weak | Replaced |
| Gas burners | Dusty | Cleaned |
What it looked like











Work completed
- Vacuumed out the duct plenum
- Removed and cleaned the gas burners and burner compartment
- Removed and cleaned the blower wheel (level 2 cleaning)
- Flushed the evaporator coil (level 2)
- Replaced the weak 5 µF capacitor
- Installed a UV light with a carbon filter
Next steps for this system
- Keep up regular filter changes to slow new dust buildup
- Replace the UV bulb on the schedule on its label
Real job from our service records. Customer names, street addresses and equipment serial numbers are left out; photos show the equipment only.
Air quality products we carry and install
We recommend these based on what we find in your system. We explain what each one does and what it does not do, and we make no medical claims.
UV light with carbon filter
Mounted inside the system near the coil. UV light limits growth on the coil and drain pan so they stay cleaner, and the carbon filter helps cut household odors.
Polarized filters
A polarized media filter captures finer dust than a standard filter without choking airflow, so less dust reaches the blower wheel and coil.
Ionizers
An in-duct ionizer charges airborne particles so they clump together and are easier for the filter to catch.
Pair any of these with duct, blower wheel and coil cleaning for the biggest difference. More about indoor air quality →
Other jobs we have documented

Condo furnace that kept shutting off on cold nights
No-heat service call
Read the job report →
Attic air handler humming and over-amping
Maintenance plan visit
Read the job report →
Winter checkup that found a failed gas valve
Winter checkup to repair
Read the job report →Seeing something similar?
Send a quick request and Josh will text you back, or pick a time online. For no heat or no AC, call.
Emergencies: call 240-483-9872, answered 24/7.