Home / Recent jobs / Washington, DC
No-heat service call · Washington, DC

Condo furnace that kept shutting off on cold nights

The tenant said the heat ran fine during the day, then quit for hours once the night got cold. We found a weak blower capacitor, dirty burners and a dirty evaporator coil, and fixed the airflow and combustion problems the same day.

Washington, DCNovember 2026Goodman gas furnace, 201740,000 BTU, 80% AFUEProperty management call
What we found

Findings and readings

  • The blower run capacitor measured 12.8 µF on a 20 µF rating, so the blower was moving less air than it should. The blower drew 5.8 A against its 4.5 A rating.
  • The burners were coated with dust and debris, and the flame showed a lot of orange instead of a steady blue.
  • The evaporator coil above the furnace was dirty, restricting airflow further.
  • With less air carrying heat away, the furnace runs hot. On long cold-weather run cycles that can trip the high-limit safety switch, which shuts the burners off until it cools down. That matches what the tenant described.
CheckReadingResult
Temperature rise63°F (rated 25–55°F)Over
Blower capacitor (before)12.8 µF on 20 µFFailed
Blower capacitor (new)19.36 µFIn range
Carbon monoxide at furnace (after)0 ppmNo CO
Flame after cleaningBlue, evenHealthy
Photos from the job

What it looked like

Original blower capacitor, rated 20 µF, measuring 12.8 µF
FOUNDOriginal blower capacitor, rated 20 µF, measuring 12.8 µF
Burners coated with dust and debris
FOUNDBurners coated with dust and debris
Dirty evaporator coil restricting airflow
FOUNDDirty evaporator coil restricting airflow
Burner assembly removed for a full cleaning
DURINGBurner assembly removed for a full cleaning
New capacitor measuring 19.36 µF
NEW PARTNew capacitor measuring 19.36 µF
Even blue flame after cleaning
AFTEREven blue flame after cleaning
The report

The service report from this visit

Every customer gets a written report like this one: the measurements, each item that needs attention, and what we recommend. Customer details are blacked out here.

Open the full report →

Service report for this job, customer details removed
What we did

Work completed

  • Removed and cleaned the entire burner assembly
  • Replaced the blower run capacitor
  • Flushed the evaporator coil with foaming coil cleaner
  • Wiped down and reinstalled the cabinet panels
  • Tested for carbon monoxide at the furnace: 0 ppm
  • Restarted the system and confirmed a healthier, more even flame
What we recommended

Next steps for this system

  • Blower wheel removal and cleaning, to restore the rest of the airflow
  • Keep an eye on the hot surface igniter, which wears with use

Real job from our service records. Customer names, street addresses and equipment serial numbers are left out; photos show the equipment only.

Manage rental or condo properties?

This call came through a property management partner. We send the same photo report to managers for every unit we visit.

Property management HVAC programs →