A pre-season checkup on a 2014 gas furnace turned up a failed gas valve, a weak blower capacitor, dirty burners and a bent gas shutoff lever. We replaced the gas valve and tuned up the burners two days later.

Gaithersburg, MDNovember 2026Goodman gas furnace, 201460,000 BTU, 80% AFUEPre-season check
What we found

Findings and readings

  • The ignition sequence failed because the gas valve had failed.
  • The blower motor capacitor, rated 12.5 µF, measured 10.55 µF. The lowest acceptable reading is about 11.9 µF.
  • The burner assembly was heavily coated with dirt and debris, which hurts combustion.
  • The lever on the gas shutoff valve was loose and bent. There was no leak, but a damaged shutoff is not something to leave.
  • Some hot spots on the heat exchanger, with no rust. Noted, not a concern today.
CheckReadingResult
Ignition sequenceNo ignitionFailed
Blower capacitor10.55 µF on 12.5 µFLow
Gas leak testNo leak foundPass
Heat exchangerHot spots, no rustMonitor
Photos from the job

What it looked like

The gas valve that failed the ignition test
FOUNDThe gas valve that failed the ignition test
Burners heavily coated with dirt and debris
FOUNDBurners heavily coated with dirt and debris
Blower capacitor measuring 10.55 µF on a 12.5 µF rating
FOUNDBlower capacitor measuring 10.55 µF on a 12.5 µF rating
Gas shutoff valve with a loose, bent lever
FOUNDGas shutoff valve with a loose, bent lever
Gas leak check: no gas detected
AFTERGas leak check: no gas detected
The report

The service report from this visit

Every customer gets a written report like this one: the measurements, each item that needs attention, and what we recommend. Customer details are blacked out here.

Open the full report →

Service report for this job, customer details removed
What we did

Work completed

  • Replaced the failed gas valve
  • Tuned up the gas burners
  • Repaired the gas shutoff valve lever at no charge
  • Cleaned the flame sensor during the inspection
What we recommended

Next steps for this system

  • Replace the weak blower capacitor
  • Clean the blower wheel and evaporator coil

Real job from our service records. Customer names, street addresses and equipment serial numbers are left out; photos show the equipment only.