Maintenance plan visit · Boyds, MD

Maintenance visit that found a disconnected flue vent

A routine visit on two 2021 Bryant furnaces. On the basement unit, the flue vent pipe was completely unattached, which is unsafe because it carries combustion gases out of the house. We reconnected it during the visit.

Boyds, MDOctober 2026Two Bryant gas furnaces, 2021Attic + basementMaintenance plan
What we found

Findings and readings

  • Basement furnace: the flue vent pipe was completely unattached and unsafe.
  • Attic furnace: an irregular flame pattern, likely from dirty burner rails and dust in the heat exchanger.
  • Dust collecting in the primary heat exchanger.
  • A hot spot on the attic igniter.
  • New dust on a blower wheel that was cleaned in May, which points to the filtration.
CheckReadingResult
Flue vent (basement)DisconnectedRepaired
Gas leak testNo leaks foundPass
CO alarmPresent, workingPass
Attic flame patternIrregularCleaned
Photos from the job

What it looked like

Flue vent connection at the basement furnace
Flue vent connection at the basement furnace
Burner assembly removed for cleaning
DURINGBurner assembly removed for cleaning
Blower wheel with new dust since May
FOUNDBlower wheel with new dust since May
Cleaning the burners on the attic furnace
DURINGCleaning the burners on the attic furnace
Burner assembly cleaned and ready to go back in
AFTERBurner assembly cleaned and ready to go back in
Even blue flames after the burner cleaning
AFTEREven blue flames after the burner cleaning
Basement blower wheel, clean
Basement blower wheel, clean
The report

The service report from this visit

Every customer gets a written report like this one: the measurements, each item that needs attention, and what we recommend. Customer details are blacked out here.

Open the full report →

Service report for this job, customer details removed
What we did

Work completed

  • Reattached and secured the flue vent pipe
  • Removed and cleaned the gas burners on both furnaces
  • Cleaned the flame sensors and igniter
  • Checked for gas leaks and confirmed a working CO alarm
What we recommended

Next steps for this system

  • A polarized filter and an ionizer, to cut the dust reaching the coil

Real job from our service records. Customer names, street addresses and equipment serial numbers are left out; photos show the equipment only.